丹佛斯电子膨胀阀控制器AK-CC750(3)
- at which point (”terminals”)
- what is connected (e.g. pressure transmitter/type/ pressure range)
8 RS8EM102 © Danfoss 02-2009
AK-CC 750
丹佛斯电子膨胀阀控制器AK-CC750
1. Controller
TypeAK-CC 750
Function
Controller for evaporator control
Application
Refrigeration appliances control
3. AK operation and accessories
TypeOperationAK-ST 500
--AccessoriesAK-PS 075AK-PS 150AccessoriesEKA 163BEKA 164B
-AccessoriesAK-OB 101A
Software for operation of AK controllersCable between PC and AK controller
Cable between zero modem cable and AK controller /Cable between PDA cable and AK controllerTransformer module 230 V / 115 V to 24 V18 VA, 24 V d.c.36 VA, 24 V d.c.
AK-operationAK - Com portAK - RS 232
Function
Application
Supply for controller
External display that can be connected to the controller module. For showing, say, the refrigeration appliancesDisplay
Display with operation buttonsCable between display and controller
Length = 2 mLength = 6 m
Real time clock for use in controllers that require a clock function, but are not wired with data communication.Real time clock with battery backup.
To be mounted in an AK controller
On the following pages there is data specific to each module.
AK-CC 750 RS8EM102 © Danfoss 02-2009
9
丹佛斯电子膨胀阀控制器AK-CC750
Common data for modules
Supply voltagePower consumption
24 V d.c. / a.c. +/- 20%AK-__ (controller)AK-XM 101, 102AK-XM 204, 205
Analog inputs
Pt 1000 ohm /0°C
Pressure transmitter type AKS 32R / AKS 2050 / AKS 32 (1-5 V)Voltage signal 0-10 VContact function (On/Off)
8 VA2 VA5 VA
Resolution: 0.1°C
Accuracy: +/- 0.5°C (between -50°C and +50°C)
Resolution:1 mV Accuracy +/- 10 mV
Max. connection of 5 pressure transmitters on one moduleOn at R < 20 ohmOff at R > 2K ohm
(Gold -plated contacts not necessary)Off: U < 2 V On: U > 10 VOff: U < 24 V On: U > 80 V4 A3 A
Min. 24 VMax. 230 V
Low and high voltage must not be connected to the same output group
Max. 240 V a.c. , Min. 48 V a.c.Max. 0.5 A, Leak < 1 mAMax. 1 AKV-40 to 70°C
-20 to 55°C ,
0 to 95% RH (non condensing) No shock influences / vibrationsPC / ABSIP10 , VBG 4
For mounting on panel wall or DIN railCa. 200 g / 500 g / 600 g
LVD tested according to EN 60730EMC tested
Immunity according to EN 61000-6-2Emission according to EN 61000-6-3UL file number: E166834
On/off supply voltage inputs
Low voltage0 / 80 V a.c./d.c.High voltage0 / 260 V a.c.
Relay outputs SPDT
AC-1 (ohmic)AC-15 (inductive)U
Solid state outputs
Can be used for loads that are cut in and out frequently, e.g. :
rail heat, fans and AKV valveDuring transportDuring operation
Ambient temperature
EnclosureMaterialDensityMounting
Weight with screw terminalsApprovals
modules in100- / 200- / controller-seriesEU low voltage directive and EMC require-ments are complied with
UL 873,
The mentioned data applies to all modules.
If data is specific, this is mentioned together with the module in question.
10 RS8EM102 © Danfoss 02-2009
AK-CC 750
丹佛斯电子膨胀阀控制器AK-CC750
Dimensions
The module dimension is 72 mm.
Controllers consist of three modules
The length of an aggregate unit = n x 72 + 8
AK-CC 750 RS8EM102 © Danfoss 02-2009 11
丹佛斯电子膨胀阀控制器AK-CC750
Controller
Function
There are several controllers in the series. The function is deter-mined by the programmed software, but outwardly the control-lers are identical – they all have the same connection possibilities:11 analog inputs for sensors, pressure transmitters, voltage signals and contact signals.
8 digital outputs, with 4 Solid state outputs and 4 relay outputsSupply voltage
24 V a.c. or d.c. to be connected to the controller.
The 24 V must not be retransmitted and used by other control-lers as it is not galvanically separated from inputs and outputs. In other words, you must use a transformer for each controller. Class II is required. The terminals must not be earthed.
The supply voltage to any extension modules is transmitted via the plug on the right-hand side.
The size of the transformer is determined by the power require-ment of the total number of modules.
The supply voltage to a pressure transmitter can be taken either from the 5 V output or from the 12 V output depending on trans-mitter type.
Data communication
If the controller is to be included in a system, communica-tion must take place via the LON connection.
The installation has to be made as mentioned in the sepa-rate instructions for LON communication.Address setting
When the controller is connected to a gateway type AKA 245, the controller’s address must be set between 1 and 119. (1-200 at AK-SM..).
Service PIN
When the controller is connected to the data communication ca-ble the gateway must have knowledge of the new controller. This is obtained by pushing the key PIN. The LED “Status” will flash fast when the gateway sends an acceptance message.
Operation
The configuration operation of the controller must take place from the software programme “Service Tool”. The program must be installed on a PC, and the PC must be connected to the controller via the network plug on the front of the unit.
Light-emitting diodes
There are two rows with LED’s. They mean:Left row:
Voltage sup …… 此处隐藏:4827字,全部文档内容请下载后查看。喜欢就下载吧 ……
相关推荐:
- [资格考试]石油钻采专业设备项目可行性研究报告编
- [资格考试]2012-2013学年度第二学期麻风病防治知
- [资格考试]道路勘测设计 绪论
- [资格考试]控烟戒烟知识培训资料
- [资格考试]建设工程安全生产管理(三类人员安全员
- [资格考试]photoshop制作茶叶包装盒步骤平面效果
- [资格考试]授课进度计划表封面(09-10下施工)
- [资格考试]麦肯锡卓越工作方法读后感
- [资格考试]2007年广西区农村信用社招聘考试试题
- [资格考试]软件实施工程师笔试题
- [资格考试]2014年初三数学复习专练第一章 数与式(
- [资格考试]中国糯玉米汁饮料市场发展概况及投资战
- [资格考试]塑钢门窗安装((专项方案)15)
- [资格考试]初中数学答题卡模板2
- [资格考试]2015-2020年中国效率手册行业市场调查
- [资格考试]华北电力大学学习实践活动领导小组办公
- [资格考试]溃疡性结肠炎研究的新进展
- [资格考试]人教版高中语文1—5册(必修)背诵篇目名
- [资格考试]ISO9001-2018质量管理体系最新版标准
- [资格考试]论文之希尔顿酒店集团进入中国的战略研
- 全国中小学生转学申请表
- 《奇迹暖暖》17-支2文学少女小满(9)公
- 2019-2020学年八年级地理下册 第六章
- 2005年高考试题——英语(天津卷)
- 无纺布耐磨测试方法及标准
- 建筑工程施工劳动力安排计划
- (目录)中国中央空调行业市场深度调研分
- 中国期货价格期限结构模型实证分析
- AutoCAD 2016基础教程第2章 AutoCAD基
- 2014-2015学年西城初三期末数学试题及
- 机械加工工艺基础(完整版)
- 归因理论在管理中的应用[1]0
- 突破瓶颈 实现医院可持续发展
- 2014年南京师范大学商学院决策学招生目
- 现浇箱梁支架预压报告
- Excel_2010函数图表入门与实战
- 人教版新课标初中数学 13.1 轴对称 (
- Visual Basic 6.0程序设计教程电子教案
- 2010北京助理工程师考试复习《建筑施工
- 国外5大医疗互联网模式分析